Features

A truly low cost, high performance solution designed to meet all of your environmental compliance and inventory management needs. The LC2000 is available for both indoor and outdoor use without requiring a secondary enclosure, supplemental heating or cooling. Outdoor enclosure options include NEMA 4 and NEMA 4X Stainless Steel.

Ultra-High Intensity Normal (Green), Product (Red) and Water (Yellow) Alarm LEDs, Green Power LED, Visible from 75’ (23 m)

Support for up to 16 leak/point level sensors

Optional Internal Impact Printer

All models include up to 16 Leak/Point Level Sensor Inputs, 2 Programmable Relay Outputs and Contact Closure Inputs, RS485 and RS232 Serial Ports.

The LC2000 is UL/cUL approved, Third-party approved, NWGLDE-listed. Pneumercator has Florida EQ numbers and California Water Board approvals.

Dimensions (W x H x D): 11.8” x 11.5” x 4.75” (300 mm x 292 mm x 121 mm)

Weight: 14 lb (6.4 kg)

Operating Temperature without Printer: -40°F to 160°F (-40°C to 70°C)

Operating Tempertature with Printer:-5°F to 140°F (-20°C to 60°C)

Humidity: 95% Non-Condensing

Enclosure Rating: Locking NEMA 12 (IP52), NEMA 4 (IP56), or NEMA 4X 304SS (IP66)

Enclosure Mount Options: Wall-Mount (Standard) or Panel-Mount (Optional)

Power Requirements: 115/230 VAC +/-15% (w/o printer) Switchable, 50-60 Hz,
20 W Max. 8-16 VDC or 16-60 VDC Optional

Memory: Configuration/Setup Data - EEPROM, 50 year data retention, no batteries
Log Reports and Real-Time Clock - Lithium Battery-Backed RAM, 5-10 year data retention

Audible Alarm: 85 db

Display: Ultra-High Intensity Normal (Green), Product (Red) and Water (Yellow) Alarm LEDs, Green Power LED, Visible from 75’ (23 m)

Communication: (1) RS-232, (1) RS-485 for Pneumercator Peripherals

Optional Communication: Internal, Secured Modem, Fax/Modem, Network Interface (Ethernet and RS232/RS485 Serial Interface) or ModBus

Sensor Capacities: 4, 8, 12 or 16 Discriminating or Non-Discriminating Sensors
All Sensor Inputs Supervised-Wiring-Ready

Standard I/O, Non-Hazardous: 2 Relays, 1 Form C, Rated 10A@120 VAC, 6A@240 VAC, w/ 2 Opto-Isolated Inputs

Optional I/O, Non-Hazardous: (1) Expansion Slot Available
4 Relays,1 Form C, Rated 10A@120 VAC, 6A @ 240 VAC, w/4 Opto-Isolated Inputs
8 Relays,1 Form A, Rated 5A@120 VAC, 5A @ 240 VAC, w/8 Opto-Isolated Inputs
16 Relays,1 Form A, Rated 5A@120 VAC, 5A @ 240 VAC

Full spec sheet is included with LC2000 Downloads.

For additional technical resources, please contact tech support at (631) 293-8450 or support@pneumercator.com.

TMSComm Software

Access Real Time Data

View current sensor alarms and statuses in easy-to-read tabular format.

Log Reports

Retrieve historical logs and generate hardcopy reports at the PC. Reports include Alarms and Events

TMSComm AUTOPOLL

AUTOPOLL, an included application with TMSComm, provides an automated polling and data collection process selectable by site and by task that includes e-mail alerts..

Alarm Notifications

Alarms include Leak/Point-Level Sensors, and System Errors. Email alerts supported.

Ease of Programming

Perform configuration and setup programming functions either on-line to the LC2000 or off-line to a file for later upload